Uniformity of air flow from the ceiling diffuser by an advanced design of the equalizing element in the plenum box with side entry
Apstrakt
The main purpose of ventilation system is to meet the requirements of thermal comfort and air quality for the occupants. HVAC designers select air supply devices by using manufacturers' data, under the assumption that the outflow from the elements is uniform and radially symmetric. Uniformity and symmetry hold only if air velocity vectors have uniform intensities and directions that are perpendicular to the diffuser inlet cross section. Unfortunately, these conditions are hardly met in the engineering practice. The most common case of diffuser installation is the flush ceiling installation, accompanied with the plenum box with side entry above the ceiling. Therefore, in the present article investigated is the influence of different geometries of the equalizing elements in the plenum box with the side entry connection on the symmetry of the jet and the flow distribution through the four-sided square ceiling diffuser. New designs of the plenum box with an inclined non-uniformly perforate...d plate and with an equalizing element with air guidance blades are proposed and evaluated numerically and experimentally. A better uniformity of the air discharge from the diffuser outlet to the ventilated room is achieved.
Izvor:
Science and Technology For The Built Environment, 2020, 26, 5, 676-686Izdavač:
- Taylor & Francis Inc, Philadelphia
Finansiranje / projekti:
- Ministry of Education, Science and Technological Development of the Republic of Serbia
DOI: 10.1080/23744731.2020.1730124
ISSN: 2374-4731
WoS: 000518718500001
Scopus: 2-s2.0-85081377177
Kolekcije
Institucija/grupa
Mašinski fakultetTY - JOUR AU - Vasić, Mihailo AU - Stevanović, Vladimir AU - Zivković, Branislav PY - 2020 UR - https://machinery.mas.bg.ac.rs/handle/123456789/3402 AB - The main purpose of ventilation system is to meet the requirements of thermal comfort and air quality for the occupants. HVAC designers select air supply devices by using manufacturers' data, under the assumption that the outflow from the elements is uniform and radially symmetric. Uniformity and symmetry hold only if air velocity vectors have uniform intensities and directions that are perpendicular to the diffuser inlet cross section. Unfortunately, these conditions are hardly met in the engineering practice. The most common case of diffuser installation is the flush ceiling installation, accompanied with the plenum box with side entry above the ceiling. Therefore, in the present article investigated is the influence of different geometries of the equalizing elements in the plenum box with the side entry connection on the symmetry of the jet and the flow distribution through the four-sided square ceiling diffuser. New designs of the plenum box with an inclined non-uniformly perforated plate and with an equalizing element with air guidance blades are proposed and evaluated numerically and experimentally. A better uniformity of the air discharge from the diffuser outlet to the ventilated room is achieved. PB - Taylor & Francis Inc, Philadelphia T2 - Science and Technology For The Built Environment T1 - Uniformity of air flow from the ceiling diffuser by an advanced design of the equalizing element in the plenum box with side entry EP - 686 IS - 5 SP - 676 VL - 26 DO - 10.1080/23744731.2020.1730124 ER -
@article{ author = "Vasić, Mihailo and Stevanović, Vladimir and Zivković, Branislav", year = "2020", abstract = "The main purpose of ventilation system is to meet the requirements of thermal comfort and air quality for the occupants. HVAC designers select air supply devices by using manufacturers' data, under the assumption that the outflow from the elements is uniform and radially symmetric. Uniformity and symmetry hold only if air velocity vectors have uniform intensities and directions that are perpendicular to the diffuser inlet cross section. Unfortunately, these conditions are hardly met in the engineering practice. The most common case of diffuser installation is the flush ceiling installation, accompanied with the plenum box with side entry above the ceiling. Therefore, in the present article investigated is the influence of different geometries of the equalizing elements in the plenum box with the side entry connection on the symmetry of the jet and the flow distribution through the four-sided square ceiling diffuser. New designs of the plenum box with an inclined non-uniformly perforated plate and with an equalizing element with air guidance blades are proposed and evaluated numerically and experimentally. A better uniformity of the air discharge from the diffuser outlet to the ventilated room is achieved.", publisher = "Taylor & Francis Inc, Philadelphia", journal = "Science and Technology For The Built Environment", title = "Uniformity of air flow from the ceiling diffuser by an advanced design of the equalizing element in the plenum box with side entry", pages = "686-676", number = "5", volume = "26", doi = "10.1080/23744731.2020.1730124" }
Vasić, M., Stevanović, V.,& Zivković, B.. (2020). Uniformity of air flow from the ceiling diffuser by an advanced design of the equalizing element in the plenum box with side entry. in Science and Technology For The Built Environment Taylor & Francis Inc, Philadelphia., 26(5), 676-686. https://doi.org/10.1080/23744731.2020.1730124
Vasić M, Stevanović V, Zivković B. Uniformity of air flow from the ceiling diffuser by an advanced design of the equalizing element in the plenum box with side entry. in Science and Technology For The Built Environment. 2020;26(5):676-686. doi:10.1080/23744731.2020.1730124 .
Vasić, Mihailo, Stevanović, Vladimir, Zivković, Branislav, "Uniformity of air flow from the ceiling diffuser by an advanced design of the equalizing element in the plenum box with side entry" in Science and Technology For The Built Environment, 26, no. 5 (2020):676-686, https://doi.org/10.1080/23744731.2020.1730124 . .