Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils
dc.creator | Genić, Srbislav | |
dc.creator | Jaćimović, Branislav M. | |
dc.creator | Jarić, Marko | |
dc.creator | Budimir, Nikola | |
dc.date.accessioned | 2022-09-19T17:08:03Z | |
dc.date.available | 2022-09-19T17:08:03Z | |
dc.date.issued | 2013 | |
dc.identifier.issn | 0017-9310 | |
dc.identifier.uri | https://machinery.mas.bg.ac.rs/handle/123456789/1652 | |
dc.description.abstract | This paper presents the results of measurements of thermal performance of 8 heat exchangers with parallel helical coils. Measurements were conducted in substations in 2 district heating systems in Serbia: Belgrade and Sremska Mitrovica. The values of fouling resistances were found to be slightly lesser than usual values for typical shell-and-tube heat exchangers with straight tubes. Analysis of thermal performance of heat exchangers showed that the shell-side heat transfer coefficient can be calculated using the correlation based on hydraulic diameter. | en |
dc.publisher | Pergamon-Elsevier Science Ltd, Oxford | |
dc.relation | Ministry of Education and Science of Serbia | |
dc.rights | restrictedAccess | |
dc.source | International Journal of Heat and Mass Transfer | |
dc.subject | Hydraulic diameter | en |
dc.subject | Helical coil | en |
dc.subject | Heat transfer coefficient | en |
dc.subject | Heat exchanger | en |
dc.subject | Fouling factor | en |
dc.title | Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils | en |
dc.type | article | |
dc.rights.license | ARR | |
dc.citation.epage | 15 | |
dc.citation.issue | 1 | |
dc.citation.other | 57(1): 9-15 | |
dc.citation.rank | aM21 | |
dc.citation.spage | 9 | |
dc.citation.volume | 57 | |
dc.identifier.doi | 10.1016/j.ijheatmasstransfer.2012.09.060 | |
dc.identifier.scopus | 2-s2.0-84867653129 | |
dc.identifier.wos | 000313466900002 | |
dc.type.version | publishedVersion |