dc.description.abstractThis paper presents the results of measurements of thermal performance of 8 heat exchangers with parallel helical coils. Measurements were conducted in substations in 2 district heating systems in Serbia: Belgrade and Sremska Mitrovica. The values of fouling resistances were found to be slightly lesser than usual values for typical shell-and-tube heat exchangers with straight tubes. Analysis of thermal performance of heat exchangers showed that the shell-side heat transfer coefficient can be calculated using the correlation based on hydraulic diameter.en
dc.publisherPergamon-Elsevier Science Ltd, Oxford
dc.relationMinistry of Education and Science of Serbia
dc.rightsrestrictedAccess
dc.sourceInternational Journal of Heat and Mass Transfer
dc.subjectHydraulic diameteren
dc.subjectHelical coilen
dc.subjectHeat transfer coefficienten
dc.subjectHeat exchangeren
dc.subjectFouling factoren
dc.titleAnalysis of fouling factor in district heating heat exchangers with parallel helical tube coilsen
dc.typearticle
dc.rights.licenseARR
dc.citation.epage15
dc.citation.issue1
dc.citation.other57(1): 9-15
dc.citation.rankaM21
dc.citation.spage9
dc.citation.volume57
dc.identifier.doi10.1016/j.ijheatmasstransfer.2012.09.060
dc.identifier.scopus2-s2.0-84867653129
dc.identifier.wos000313466900002
dc.type.versionpublishedVersion


Документи

Thumbnail

Овај документ се појављује у следећим колекцијама

Приказ основних података о документу