Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils
Само за регистроване кориснике
2013
Чланак у часопису (Објављена верзија)
Метаподаци
Приказ свих података о документуАпстракт
This paper presents the results of measurements of thermal performance of 8 heat exchangers with parallel helical coils. Measurements were conducted in substations in 2 district heating systems in Serbia: Belgrade and Sremska Mitrovica. The values of fouling resistances were found to be slightly lesser than usual values for typical shell-and-tube heat exchangers with straight tubes. Analysis of thermal performance of heat exchangers showed that the shell-side heat transfer coefficient can be calculated using the correlation based on hydraulic diameter.
Кључне речи:
Hydraulic diameter / Helical coil / Heat transfer coefficient / Heat exchanger / Fouling factorИзвор:
International Journal of Heat and Mass Transfer, 2013, 57, 1, 9-15Издавач:
- Pergamon-Elsevier Science Ltd, Oxford
Финансирање / пројекти:
- Ministry of Education and Science of Serbia
DOI: 10.1016/j.ijheatmasstransfer.2012.09.060
ISSN: 0017-9310
WoS: 000313466900002
Scopus: 2-s2.0-84867653129
Институција/група
Inovacioni centarTY - JOUR AU - Genić, Srbislav AU - Jaćimović, Branislav M. AU - Jarić, Marko AU - Budimir, Nikola PY - 2013 UR - https://machinery.mas.bg.ac.rs/handle/123456789/1652 AB - This paper presents the results of measurements of thermal performance of 8 heat exchangers with parallel helical coils. Measurements were conducted in substations in 2 district heating systems in Serbia: Belgrade and Sremska Mitrovica. The values of fouling resistances were found to be slightly lesser than usual values for typical shell-and-tube heat exchangers with straight tubes. Analysis of thermal performance of heat exchangers showed that the shell-side heat transfer coefficient can be calculated using the correlation based on hydraulic diameter. PB - Pergamon-Elsevier Science Ltd, Oxford T2 - International Journal of Heat and Mass Transfer T1 - Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils EP - 15 IS - 1 SP - 9 VL - 57 DO - 10.1016/j.ijheatmasstransfer.2012.09.060 ER -
@article{ author = "Genić, Srbislav and Jaćimović, Branislav M. and Jarić, Marko and Budimir, Nikola", year = "2013", abstract = "This paper presents the results of measurements of thermal performance of 8 heat exchangers with parallel helical coils. Measurements were conducted in substations in 2 district heating systems in Serbia: Belgrade and Sremska Mitrovica. The values of fouling resistances were found to be slightly lesser than usual values for typical shell-and-tube heat exchangers with straight tubes. Analysis of thermal performance of heat exchangers showed that the shell-side heat transfer coefficient can be calculated using the correlation based on hydraulic diameter.", publisher = "Pergamon-Elsevier Science Ltd, Oxford", journal = "International Journal of Heat and Mass Transfer", title = "Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils", pages = "15-9", number = "1", volume = "57", doi = "10.1016/j.ijheatmasstransfer.2012.09.060" }
Genić, S., Jaćimović, B. M., Jarić, M.,& Budimir, N.. (2013). Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils. in International Journal of Heat and Mass Transfer Pergamon-Elsevier Science Ltd, Oxford., 57(1), 9-15. https://doi.org/10.1016/j.ijheatmasstransfer.2012.09.060
Genić S, Jaćimović BM, Jarić M, Budimir N. Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils. in International Journal of Heat and Mass Transfer. 2013;57(1):9-15. doi:10.1016/j.ijheatmasstransfer.2012.09.060 .
Genić, Srbislav, Jaćimović, Branislav M., Jarić, Marko, Budimir, Nikola, "Analysis of fouling factor in district heating heat exchangers with parallel helical tube coils" in International Journal of Heat and Mass Transfer, 57, no. 1 (2013):9-15, https://doi.org/10.1016/j.ijheatmasstransfer.2012.09.060 . .